New Energy Star Qualified Homes Version 3.0 Guidelines

National Program Requirements

NY State Energy Conversation Construction Code of NYS-2010 FAQ

Thermal Encloser System Guidebook

Water Management Guidebook

HVAC Quality Installation Guide

Inspection Checklists

2010 Energy Star Labeled Homes Guidelines

Cooling Equipment
(minimum)
A/C 14.5 SEER / 12 EER Heat Pump 14.5 SEER / 12 EER 8.5 HSPF
Heating Equipment
(minimum)
ENERGY STAR Qualified Gas Furnace 90 AFUE; or
ENERGY STAR Qualified Gas or Oil boiler 85 AFUE; or
ENERGY STAR Qualified 8.5 HSPF Heat Pump; or
Oil Furnace 85 AFUE
Thermostat ENERGY STAR Labeled programmable
Ductwork Leakage maximum: 6 CFM25/ 100 sq. ft. of conditioned
floor area, Insulation minimum: R-8 in unconditioned spaces
Envelope Leakage 5 ACH50 maximum; Completed Thermal Bypass Checklist
Flat Ceilings (minimum) R-38 (R-30 with raised heel truss or equivalent)
Vaulted Ceilings (minimum) R-30 (limited to 500 sq. ft. of ceiling area)
Walls (minimum) R-13
Floor (minimum) R-19
Basement or Crawlspace Walls (minimum) R-10 continuous or R-13 cavity
Slab Edge (minimum) R-10 for 2 feet minimum
Windows (maximum) U-Factor Windows < .35 and any SHGC;
Skylights < .60 and < any SHGC
Water Heater EF (minimum) Gas or Oil: 40 Gal = 0.61 / 50 Gal =.59 / 75 Gal =0.54
OR: Instantaneous Water Heater or Indirect-Fired Storage
Tank with boiler
Lighting and Appliances
Electrical kWh Savings
500 kWh or 650 kWh savings required for all NYESLH
Mechanical Ventilation Automatically controlled mechanical ventilation shall be
installed according to NYESLH Technical Specifications
Combustion Safety Testing Required for all NYESLH ( See NYESLH Technical
Specifications)